De Victron Multiplus-II laad in 4 fases.
Bulk
Entered when charger is started. Constant current is applied until nominal battery voltage is reached, depending on temperature
and input voltage, after which constant power is applied up to the point where excessive gassing starts. This is at 14.4 V for
temperature compensated for lead acid batteries.
Battery Safe
The voltage applied to the battery is raised gradually until the set absorption voltage is reached. The Battery Safe Mode is part of
the calculated absorption time.
Absorption
The absorption period is dependent on the bulk period. The maximum absorption time is the set Maximum Absorption time.
De accu wordt geladen met constante spanning en dalende stroom tot deze volledig is geladen.
Float
Float voltage is applied to keep the battery fully charged.
Storage
After one day of float charge, the output voltage is reduced to the storage level. This is 1.2 V. This will limit water loss to a
minimum when the battery is stored for the winter season. After an adjustable time (default = 7 days), the charger will enter
Repeated Absorption mode for an adjustable time (default = one hour) to ’refresh’ the battery.